Besam Addendum for VersaMax 2.0 Touchless

ASSA ABLOY VersaMax™ ICU Touchless Automatic Door Package

Installation Manual Addendum

2-Panel and Telescopic Door Systems

Overview

This installation addendum provides supplemental instructions for installing the VersaMax ICU Touchless Automatic Door Package on:

  • 2-panel door systems
  • Telescopic door systems

The addendum includes:

  • Hardware installation
  • Touchless switch installation
  • Safety beam installation
  • Wiring diagrams
  • Program selector configuration
  • Access control integration
  • Signage requirements

This document is intended to be used alongside:

  • VersaMax ICU/CCU Equal Panel Installation Manual (1016377)
  • VersaMax ICU/CCU Telescopic Panel Installation Manual (1016378)

Compatible Models

The VersaMax™ Touchless Automatic Door option can be installed on any:

  • ASSA ABLOY ICU door package
  • ASSA ABLOY CCU door package

Safety & Compliance

Safety Standards

The VersaMax system is designed to comply with:

  • ANSI automatic door safety standards
  • AAADM inspection requirements
  • FCC Part 15 / EN 61000-6-3 emissions standards

Recommended Safety Practices

  • Annual AAADM inspections
  • Maintain all decals and safety labels
  • Verify operation after servicing
  • Ensure proper grounding and wiring

Environmental Requirements

Proper disposal of:

  • Electronics
  • Batteries
  • Packaging materials

must comply with local environmental regulations.

Required Tools

Installation Tools

  • 10mm wrench
  • Rubber mallet
  • Channellock pliers
  • Torx screwdrivers
  • Drill & drill bits
  • 6-32 drill tap
  • 1-1/4″ hole saw
  • Screwdriver set
  • Tape measure

Door Installation Overview

The installation process includes:

  1. Unpacking
  2. Hardware installation
  3. Sensor installation
  4. Wiring connections
  5. Switch installation
  6. Final setup and testing

Unpacking Instructions

Remove all:

  • Packaging material
  • Shipping protection
  • Scrap materials

before installation to prevent interference with door operation.

Dispose of all materials according to local regulations.

Hardware Installation

Transmission Bracket Installation

Steps

  1. Install the transmission bracket onto the factory-installed belt holder bracket.
  2. Use:
    • M6 Torx pan head screws
    • M6 nuts
    • washers
  3. Attach the transmission bracket assembly to the carrier.

Carrier Orientation

Door Configuration

Mounting Location

RH FBO / LH FSL / LH SA

Lead end of carrier

LH FBO / RH FSL / RH SA

Trail end of carrier

Overhead Presence Sensor Installation

Overhead presence sensors must be installed:

  • On both sides of the package
  • Centered in the clear door opening

Use the provided templates and instructions for:

  • Mounting
  • Wiring
  • Sensor alignment

(Page 7 diagram illustrates correct positioning.)

Safety Beam Installation (Optional)

Breakout Beam Installation

Install breakout safety beams according to the Breakout Beam Kit instructions.

Standard Application Dimensions

(Page 9 diagram)

Measurement

Value

Typical height

55″

Lower beam

24″

Mid beam

36″

Overall beam height

43″

Surface-Applied Safety Beams

(Page 10 diagram)

Installation Notes

  • Jambs are pre-drilled
  • Drill (8) additional 1/8″ holes as required
  • Use the safety beam housing as a template
  • Install mounting brackets supplied with package

Once complete:

  • Safety beams should be mounted on both sides of the package
  • Wiring should be concealed and secured

Touchless Switch Installation

Supported Configurations

  • Jamb-mounted touchless switch
  • Wall-mounted touchless switch

(Page 11 diagrams show both versions.)

Installation Notes

If factory-prepped jamb switches are selected:

  • Rectangular cutouts are pre-drilled
  • Mounting holes are field-tapped

If wall-mounted:

  • All preparation is completed in the field

3-Position Program Selector Switch

Selector Positions

Position

Function

Closed

Disables activation units

AUTO

Normal two-way operation

OPEN

Holds door permanently open

CLOSED Mode

  • Inner and outer activation sensors disabled
  • Door may still open using:
    • Emergency push button
    • Key switch

AUTO Mode

Standard operation:

  • Two-way traffic
  • Inner and outer sensors active

OPEN Mode

Door remains permanently open.

Important

OPEN mode is only available when:

  • Connected to building fire alarm system

If smoke seals are installed without fire alarm integration:

  • Hold-open functionality is disabled

Positive Latch & Access Control Wiring

The manual includes wiring diagrams for:

  • Positive latch systems
  • Access control systems
  • Hold-open functions
  • Emergency close systems
  • No program switch configurations

Diagram Variants

(Page 13–19)

Configuration

Page

Positive latch + access control + hold-open

13

Positive latch + access control

14

Access control + hold-open

15

Access control only

16

Positive latch, no hold-open

17

Positive latch + hold-open

18

No program switch positive latch

19

Power Supply Installation

Electrical Connection

  1. Attach 120V power supply to power box
  2. Plug power cord into controller
  3. Verify grounding connection

(Page 20 diagram illustrates power box layout.)

Electronic Shutter Strike Adjustment

Adjustment Procedure

  1. Loosen the two M6 screws
  2. Move shutter strike assembly
  3. Retighten screws
  4. Verify strike plate movement

Important

The strike plate must move freely after adjustment.

Cover & End Cap Installation

Final Assembly

  1. Close cover
  2. Align end cap holes
  3. Secure using Button Head Torx screws

If end plate seams are uneven:

  • Push outer plate inward
  • Install Phillips Pan Head Tek screw

(Page 21 diagrams show correct assembly.)

Signage Requirements

Required decals include:

  • “Automatic Door – Stand Clear”
  • “Caution – Automatic Door”

(Page 22 diagram shows placement locations.)

System Notes

  • Required holes are pre-drilled except for optional kits
  • Presence sensors must be centered in clear openings
  • Jamb-mounted touchless switches with electronic shutter strikes must be mounted at:
    • 48″ centerline to prevent interference.

Maintenance Recommendations

  • Test all sensors after installation
  • Verify access control operation
  • Inspect safety beams regularly
  • Confirm emergency functions operate properly
  • Maintain all signage and labels