ASSA ABLOY VersaMax™ ICU Touchless Automatic Door Package
Installation Manual Addendum
2-Panel and Telescopic Door Systems
Overview
This installation addendum provides supplemental instructions for installing the VersaMax ICU Touchless Automatic Door Package on:
- 2-panel door systems
- Telescopic door systems
The addendum includes:
- Hardware installation
- Touchless switch installation
- Safety beam installation
- Wiring diagrams
- Program selector configuration
- Access control integration
- Signage requirements
This document is intended to be used alongside:
- VersaMax ICU/CCU Equal Panel Installation Manual (1016377)
- VersaMax ICU/CCU Telescopic Panel Installation Manual (1016378)
Compatible Models
The VersaMax™ Touchless Automatic Door option can be installed on any:
- ASSA ABLOY ICU door package
- ASSA ABLOY CCU door package
Safety & Compliance
Safety Standards
The VersaMax system is designed to comply with:
- ANSI automatic door safety standards
- AAADM inspection requirements
- FCC Part 15 / EN 61000-6-3 emissions standards
Recommended Safety Practices
- Annual AAADM inspections
- Maintain all decals and safety labels
- Verify operation after servicing
- Ensure proper grounding and wiring
Environmental Requirements
Proper disposal of:
- Electronics
- Batteries
- Packaging materials
must comply with local environmental regulations.
Required Tools
Installation Tools
- 10mm wrench
- Rubber mallet
- Channellock pliers
- Torx screwdrivers
- Drill & drill bits
- 6-32 drill tap
- 1-1/4″ hole saw
- Screwdriver set
- Tape measure
Door Installation Overview
The installation process includes:
- Unpacking
- Hardware installation
- Sensor installation
- Wiring connections
- Switch installation
- Final setup and testing
Unpacking Instructions
Remove all:
- Packaging material
- Shipping protection
- Scrap materials
before installation to prevent interference with door operation.
Dispose of all materials according to local regulations.
Hardware Installation
Transmission Bracket Installation
Steps
- Install the transmission bracket onto the factory-installed belt holder bracket.
- Use:
- M6 Torx pan head screws
- M6 nuts
- washers
- Attach the transmission bracket assembly to the carrier.
Carrier Orientation
Door Configuration | Mounting Location |
RH FBO / LH FSL / LH SA | Lead end of carrier |
LH FBO / RH FSL / RH SA | Trail end of carrier |
Overhead Presence Sensor Installation
Overhead presence sensors must be installed:
- On both sides of the package
- Centered in the clear door opening
Use the provided templates and instructions for:
- Mounting
- Wiring
- Sensor alignment
(Page 7 diagram illustrates correct positioning.)
Safety Beam Installation (Optional)
Breakout Beam Installation
Install breakout safety beams according to the Breakout Beam Kit instructions.
Standard Application Dimensions
(Page 9 diagram)
Measurement | Value |
Typical height | 55″ |
Lower beam | 24″ |
Mid beam | 36″ |
Overall beam height | 43″ |
Surface-Applied Safety Beams
(Page 10 diagram)
Installation Notes
- Jambs are pre-drilled
- Drill (8) additional 1/8″ holes as required
- Use the safety beam housing as a template
- Install mounting brackets supplied with package
Once complete:
- Safety beams should be mounted on both sides of the package
- Wiring should be concealed and secured
Touchless Switch Installation
Supported Configurations
- Jamb-mounted touchless switch
- Wall-mounted touchless switch
(Page 11 diagrams show both versions.)
Installation Notes
If factory-prepped jamb switches are selected:
- Rectangular cutouts are pre-drilled
- Mounting holes are field-tapped
If wall-mounted:
- All preparation is completed in the field
3-Position Program Selector Switch
Selector Positions
Position | Function |
Closed | Disables activation units |
AUTO | Normal two-way operation |
OPEN | Holds door permanently open |
CLOSED Mode
- Inner and outer activation sensors disabled
- Door may still open using:
- Emergency push button
- Key switch
AUTO Mode
Standard operation:
- Two-way traffic
- Inner and outer sensors active
OPEN Mode
Door remains permanently open.
Important
OPEN mode is only available when:
- Connected to building fire alarm system
If smoke seals are installed without fire alarm integration:
- Hold-open functionality is disabled
Positive Latch & Access Control Wiring
The manual includes wiring diagrams for:
- Positive latch systems
- Access control systems
- Hold-open functions
- Emergency close systems
- No program switch configurations
Diagram Variants
(Page 13–19)
Configuration | Page |
Positive latch + access control + hold-open | 13 |
Positive latch + access control | 14 |
Access control + hold-open | 15 |
Access control only | 16 |
Positive latch, no hold-open | 17 |
Positive latch + hold-open | 18 |
No program switch positive latch | 19 |
Power Supply Installation
Electrical Connection
- Attach 120V power supply to power box
- Plug power cord into controller
- Verify grounding connection
(Page 20 diagram illustrates power box layout.)
Electronic Shutter Strike Adjustment
Adjustment Procedure
- Loosen the two M6 screws
- Move shutter strike assembly
- Retighten screws
- Verify strike plate movement
Important
The strike plate must move freely after adjustment.
Cover & End Cap Installation
Final Assembly
- Close cover
- Align end cap holes
- Secure using Button Head Torx screws
If end plate seams are uneven:
- Push outer plate inward
- Install Phillips Pan Head Tek screw
(Page 21 diagrams show correct assembly.)
Signage Requirements
Required decals include:
- “Automatic Door – Stand Clear”
- “Caution – Automatic Door”
(Page 22 diagram shows placement locations.)
System Notes
- Required holes are pre-drilled except for optional kits
- Presence sensors must be centered in clear openings
- Jamb-mounted touchless switches with electronic shutter strikes must be mounted at:
- 48″ centerline to prevent interference.
Maintenance Recommendations
- Test all sensors after installation
- Verify access control operation
- Inspect safety beams regularly
- Confirm emergency functions operate properly
- Maintain all signage and labels