Besam CSD 120 ELECTRA 150

How to install, adjust and power up Besam CSD 120 ELECTRA 150 Automatic Door System Wiring Diagram & Connection Reference

 

Besam Electra 150 Connection Diagram

Model: Electra 150
Drawing Number: A-10102
Date: March 1987
Revision Date: August 1987Source:

CSD-120 Controller (Part No. 620115)

Power Input

TB1

  • Terminal 1: Neutral
  • Terminal 2: Line (110V–60Hz Mains)

Fuse Ratings

  • F1: 4A
  • F2: 1A

Opening Hold Time Adjustment

Adjustable control:

  • Minimum
  • Maximum

Grounding

Earth cable must be connected to the operator back plate.

TB2 Connections

Opening Circuit

TB2 Terminals 4–7

Terminal

Function

4

Opening

5

0V (-)

6

15–20V DC

7

0V (+)

Safety Mat / Slave Connections

TB3 Terminals 8–11

Terminal

Function

8

Safety Mat

9

Safety Mat

10

0V (+)

11

Slave

Scanner Connections

RBI / RRI Scanner

RRI: Select Scan
RBI: Commander

TB2 Scanner Wiring

Terminal

Wire Color

4

Green

5

White

6

Black

7

Red

CSD-5 Controller (Part No. 620114)

Power Input

TB1

Terminal

Function

1

Neutral

2

Line (110V–60Hz Mains)

Fuse Rating

  • F1: 4A

Grounding

Earth cable must be connected to operator back plate.

Additional Notes

  • Use 15–20V DC for opening circuit connections.
  • Ensure all earth ground connections are securely bonded to the operator back plate.
  • Safety mat and slave device wiring connect through TB3.
  • Scanner devices (RBI/RRI) connect through TB2 using the specified wire color sequence.
  • Opening hold time is adjustable via the controller potentiometer.

This drawing is essentially a wiring schematic for the Besam Electra 150 automatic door operator, showing controller connections, scanner wiring, safety mat inputs, power requirements, grounding requirements, and hold-open timing adjustment.