Besam MP Wiring

How to install, adjust and power up Besam MP Wiring Automatic Door System Wiring Diagram & Connection Reference

 

Besam SwingMaster MP Wiring Guide

CUP Control Unit Wiring & Terminal Connections

Document: SwingMaster MP – Wiring the CUP Control Unit
Document Number: US23-0186-01

Overview

This wiring diagram illustrates the connections for the Besam SwingMaster MP CUP Control Unit, including:

  • Main power connections
  • Activation devices
  • Safety sensors
  • Motion detectors
  • Key switches
  • Door position switches
  • Lock outputs
  • EXS Extension Unit
  • Backup battery connections
  • Program selector switch

CUP Control Unit Components

Connection Points

  1. Cam / Switch Cable Connector

Connects the operator cam and switch assembly.

  1. Motor Cable Connector

Connects the drive motor to the control board.

  1. EXS Extension Unit Connectors

Used when installing the optional EXS expansion module.

  1. Revolution Counter Connector

Connects the operator revolution counter cable.

  1. TB1 Terminal Block

Primary field wiring terminal block.

  1. TB2 Terminal Block

Backup battery and EUS connections.

Fuse Ratings

Fuse

Rating

F1

2A

F2

10A

Important: Replace fuses only with the same rating.

Source: Diagram note

Main Power Connection

Incoming Power

Connection

Description

L

Line

N

Neutral

GND

Ground

Ground connection must be properly bonded before operation.

PMD Programming Module

The PMD programming module connects directly to the CUP controller.

Important Note

After connecting the PMD:

  1. Enter the PIN code.
  2. Access programming functions.
  3. Adjust operational settings as required.

TB1 Terminal Assignments

CUP / TB1 Terminal Block

Terminal

Function

1

Key Operate

2

Presence Sensor

3

Inner Operate

4

0 VDC

5

Presence Detection

6

Kill

7

Off

8

Contact Mat

9

Spare

10

Spare

11

0 VDC

12

Programmable Door / Position Switches

13

Programmable Door / Position Switches

14

Programmable Door / Position Switches

15

Programmable Door / Position Switches

16

24 VDC Lock Output (330 mA)

17

24 VDC Lock Output (330 mA)

18

24 VDC Stabilized Output (180 mA)

19

24 VDC Stabilized Output (180 mA)

20

18 VDC Stabilized Output (330 mA)

Source: Wiring diagram terminal strip

Activation Devices

Push-To-Open Plate

The diagram shows a standard push plate connected to:

  • Inner Operate
  • Overhead Presence Detection (OPD)

Activation causes the door to open automatically.

Key Switch

A keyed switch may be connected to the:

Key Operate input.

Typical uses:

  • Restricted access
  • Staff-only entrances
  • Security-controlled doors

Motion Detector Connections

A motion detector can be connected to the CUP controller.

The detector output is wired through the programmable input terminals.

Applications include:

  • Approach activation
  • Presence sensing
  • Automatic opening

Safety Devices

Presence Sensor

Connected through:

  • Presence Sensor input
  • Presence Detection input

Used to prevent door movement when a person is within the detection zone.

Contact Safety Mat

Connected to:

TB1 Terminal 8

Used to stop or reverse the door when occupied.

EXS Extension Unit (Optional)

The optional EXS Expansion Unit provides additional control inputs.

EXS Terminals

Terminal

Function

1

Exit

2

Outer Impulse

3

Open / Close Impulse

4

Interlocking Out

5

0 VDC

6

Interlocking In

7

18 VDC

8

0 VDC

Source: EXS section of diagram

Slave Operator Configuration

When using paired operators:

CUP “Slave” Connections

Connect synchronization wiring between:

  • Master operator
  • Slave operator

Programming Notes:

  • PMD Function 08 = 00
  • PMD Function 09 = 00
  • PMD Function 16 = Same value as Master

This ensures coordinated operation between paired doors.

Three-Position Program Switch

The diagram shows a three-position selector switch connected to TB1.

Installation Requirements

  1. Mount where easily accessible.
  2. Mount within view of the controlled door.
  3. Ensure the user can see the door while operating the switch.

Switch Functions

Hold Open

Short terminals:

3 & 4

Door remains open.

Hold Closed

Short terminals:

4 & 8

Door remains closed.

Important Safety Warning

If the selector switch is placed in the OFF position and Push Reactivation is enabled, the door will continue to operate when activated.

Verify operating mode during commissioning and testing.

Notes

  • VisionPulse and VisionPulse S sensor wiring is covered in separate manuals.
  • Always verify correct grounding and fuse ratings.
  • Ensure safety devices are tested after installation.
  • Follow ANSI/BHMA requirements when commissioning automatic doors.