Elite OC-904C T Control Connection Matrix


Overview

The Elite OC-904C T Connection Matrix provides wiring instructions for integrating the Elite OC-904C T safety controller with a variety of automatic door operators. The controller supports:

  • Stall Detection
  • Activation
  • Safety Monitoring
  • Motor Monitoring
  • Test Inputs
  • Knowing Act Applications

Verify proper operation of the automatic door system before installing the Elite controller. If Knowing Act functionality is enabled (DIP Switch 3 ON), Push-N-Go must be disabled on the automatic door system.

OC-904C T Wire Colors

Function

Wire Color

Stall

Green

Activate

Yellow

Safety

Blue

Motor Negative (-)

Black

Motor Positive (+)

Red

Power

Brown

Power

Orange

Test Input (-)

Red/Blue

Test Input (+)

Gray/Pink

Knowing Act Input

Purple

DIP Switch Settings

Standard Configuration

  • Switches 1 through 8: OFF (Down)
  • Exceptions noted in OEM installation notes

Knowing Act Applications

  • Switch 3: ON (Up)

Non-Supervised Automatic Door Systems

  • Switch 4: ON (Up)
  • Switch 5: OFF (Down)
  • Switch 6: ON (Up)

Important Knowing Act Note

Connect Knowing Act devices to:

  • Purple
  • White/Purple

Do not connect the Purple and White/Purple wires directly to the door control.

Besam Operators

300 / 400

Connections

Function

Connection

Stall

Pins 15 & 16

Activate

Pins 13 & 14

Safety

Pins 11 & 12

Motor (-)

Motor Negative

Motor (+)

Motor Positive

Power

Pin 7

Power

Pin 8

Installation Notes

  • Singles require jumper from Pin 17 to Pin 18.
  • Set DIP Switch 2 to N.C. (Up).
  • LH Operator: Black motor wire positive.
  • RH Operator: White motor wire positive.
  • When using ON/OFF/HOLD switch, route one yellow wire through switch.

MP / CUP (V6.4 OHC Only)

Programming

  • F11 = 3°
  • F13 = A
  • F14 = A
  • F16 = 00
  • F17 = 00
  • F18 = 00
  • F19 = B
  • F20 = B

Pair Operation

Use synchronization lines between master and slave controllers.

900

Notes

  • If no Besam synchronization cable is present, add sync lines from:
    • Master to Slave TB1 Pins 1, 2, 3, and 7.

SW-100

Installation Notes

  • Remove jumper from Pin 1 to Pin 3 on EXU-SA board.
  • Simultaneous pairs require Besam synchronization cable.
  • Set DIP Switch 2 to N.C. (Up).

SW-200

Installation Notes

  • Remove jumper from Pin 1 to Pin 3.
  • Install jumper from Pin 1 to Pin 2.
  • Simultaneous pairs require Besam synchronization cable.
  • Set DIP Switch 2 to N.C. (Up).

Dorma Operators

ED-400

Function

Connection

Stall

SWING & GND

Activate

TRIG & GND

Safety

Presence & GND

Motor

DATA

Power

Any +24V

Ground

Any GND

Notes

For pairs, install synchronization wire from TRIG to TRIG.

ED-700 (Old Style)

Refer to Horton 4190 connection requirements.

ED100 / ED250

Contact OPTEX Technical Support.

Doromatic

Astroswing

Function

Connection

Stall

Purple & Gray

Activate

Yellow & Gray

Safety

Blue & Gray

Notes

Set DOM control selector switch to:

  • Super Nova Slow
    or
  • Super Nova Stop

Gyrotech / Nabco

300 / 400 Analog

Notes

Set door control slide switch to Swing Safe.

Magnum Control

Notes

Wire colors at J5 Pins 1 and 2 may be reversed.

Pin 2 is always the positive motor lead.

U-19 Control

Notes

  • Red and Black wires connect before handing harness.
  • For simultaneous pairs, all Elite wires except Red and Black connect to master control.
  • Master is identified by blue wire on Pin 10.

Horton

4160 Control

Notes

Simultaneous pairs require DPDT relays to isolate safety inputs.

Contact OPTEX for additional details.

4190 Control (Including Rev J)

Notes

Alternative Red and Black wire connections may be wired the same as the 4160 control.

Hunter

FA-8 Old Style

Notes

  • LH Operator: Blue wire positive.
  • RH Operator: Red wire positive.

FA-8 New Style

Uses Sensor + and Sensor – inputs.

Keane Monroe

K-Control

Standard wiring connections shown in matrix.

8000

Notes

  • Set DIP Switch 2 to N.C. (Up).
  • Program AUX1 Input and Output for BEA Bodyguard.
  • On pairs connect all wires in parallel to master except Green.
  • Green stall wire must connect to both master and slave.

LCN

2500 / 9300 Series

Notes

Use LCN Retro Harness:

Part Number: 761469

Wire the same as Doromatic Astroswing installations.

Motion Access

Condor 506

Uses J-9 terminal connections for all functions.

Quad Systems

ES-500

Uses CN2 and CN6 connections for activation, safety, power, and motor monitoring.

Stanley

Tandem L-Shape Control

Notes

  • On six-pin Molex connector:
    • Mat Safety input aligns with Yellow and Orange wires.
    • Stall Safety input is adjacent.
  • Select Timer Logic mode.

MP (HDLE) Control

Notes

  • Magicswing: Black motor wire is positive.
  • MagicForce:
    • RH Operator: Black positive.
    • LH Operator: White positive.
  • Set Stanley S-2 switches 1 and 3 OFF.

521 Control

Option 1 – Motor Monitoring

Observe motor polarity requirements.

Option 2 – Data Monitoring

Install:

  • 300Ω
  • 5 Watt resistor

between TB1 Pin 1 and Pin 8.

Set Safety Logic to Sensor.

Tormax

TDA

Notes

For simultaneous pairs or double egress applications, contact OPTEX for additional wiring instructions.

iMotion 1301

Connections shown apply to single-door installations.

For simultaneous pairs or double egress applications, contact OPTEX.

TTX2 Smart Drive

Wiring

Function

Connection

Stall

Pins 14 & 15

Activate

Pins 4 & 5

Safety

Pins 18 & 19

Motor (-)

Pin 11

Motor (+)

Pin 12

Power

Pin 20

Power

Pin 17

Programming

On TTX:

  • Solid 2 → Flashing 2
  • Solid 4 → Flashing 2

On 905 Controller:

  • DIP 1 = Up
  • DIP 2 = Up
  • DIP 4 = Down

Pairs may require DPDT relays to isolate activation and safety inputs.