Elite OC-904C T Control Connection Matrix
Overview
The Elite OC-904C T Connection Matrix provides wiring instructions for integrating the Elite OC-904C T safety controller with a variety of automatic door operators. The controller supports:
- Stall Detection
- Activation
- Safety Monitoring
- Motor Monitoring
- Test Inputs
- Knowing Act Applications
Verify proper operation of the automatic door system before installing the Elite controller. If Knowing Act functionality is enabled (DIP Switch 3 ON), Push-N-Go must be disabled on the automatic door system.
OC-904C T Wire Colors
Function | Wire Color |
Stall | Green |
Activate | Yellow |
Safety | Blue |
Motor Negative (-) | Black |
Motor Positive (+) | Red |
Power | Brown |
Power | Orange |
Test Input (-) | Red/Blue |
Test Input (+) | Gray/Pink |
Knowing Act Input | Purple |
DIP Switch Settings
Standard Configuration
- Switches 1 through 8: OFF (Down)
- Exceptions noted in OEM installation notes
Knowing Act Applications
- Switch 3: ON (Up)
Non-Supervised Automatic Door Systems
- Switch 4: ON (Up)
- Switch 5: OFF (Down)
- Switch 6: ON (Up)
Important Knowing Act Note
Connect Knowing Act devices to:
- Purple
- White/Purple
Do not connect the Purple and White/Purple wires directly to the door control.
Besam Operators
300 / 400
Connections
Function | Connection |
Stall | Pins 15 & 16 |
Activate | Pins 13 & 14 |
Safety | Pins 11 & 12 |
Motor (-) | Motor Negative |
Motor (+) | Motor Positive |
Power | Pin 7 |
Power | Pin 8 |
Installation Notes
- Singles require jumper from Pin 17 to Pin 18.
- Set DIP Switch 2 to N.C. (Up).
- LH Operator: Black motor wire positive.
- RH Operator: White motor wire positive.
- When using ON/OFF/HOLD switch, route one yellow wire through switch.
MP / CUP (V6.4 OHC Only)
Programming
- F11 = 3°
- F13 = A
- F14 = A
- F16 = 00
- F17 = 00
- F18 = 00
- F19 = B
- F20 = B
Pair Operation
Use synchronization lines between master and slave controllers.
900
Notes
- If no Besam synchronization cable is present, add sync lines from:
- Master to Slave TB1 Pins 1, 2, 3, and 7.
SW-100
Installation Notes
- Remove jumper from Pin 1 to Pin 3 on EXU-SA board.
- Simultaneous pairs require Besam synchronization cable.
- Set DIP Switch 2 to N.C. (Up).
SW-200
Installation Notes
- Remove jumper from Pin 1 to Pin 3.
- Install jumper from Pin 1 to Pin 2.
- Simultaneous pairs require Besam synchronization cable.
- Set DIP Switch 2 to N.C. (Up).
Dorma Operators
ED-400
Function | Connection |
Stall | SWING & GND |
Activate | TRIG & GND |
Safety | Presence & GND |
Motor | DATA |
Power | Any +24V |
Ground | Any GND |
Notes
For pairs, install synchronization wire from TRIG to TRIG.
ED-700 (Old Style)
Refer to Horton 4190 connection requirements.
ED100 / ED250
Contact OPTEX Technical Support.
Doromatic
Astroswing
Function | Connection |
Stall | Purple & Gray |
Activate | Yellow & Gray |
Safety | Blue & Gray |
Notes
Set DOM control selector switch to:
- Super Nova Slow
or - Super Nova Stop
Gyrotech / Nabco
300 / 400 Analog
Notes
Set door control slide switch to Swing Safe.
Magnum Control
Notes
Wire colors at J5 Pins 1 and 2 may be reversed.
Pin 2 is always the positive motor lead.
U-19 Control
Notes
- Red and Black wires connect before handing harness.
- For simultaneous pairs, all Elite wires except Red and Black connect to master control.
- Master is identified by blue wire on Pin 10.
Horton
4160 Control
Notes
Simultaneous pairs require DPDT relays to isolate safety inputs.
Contact OPTEX for additional details.
4190 Control (Including Rev J)
Notes
Alternative Red and Black wire connections may be wired the same as the 4160 control.
Hunter
FA-8 Old Style
Notes
- LH Operator: Blue wire positive.
- RH Operator: Red wire positive.
FA-8 New Style
Uses Sensor + and Sensor – inputs.
Keane Monroe
K-Control
Standard wiring connections shown in matrix.
8000
Notes
- Set DIP Switch 2 to N.C. (Up).
- Program AUX1 Input and Output for BEA Bodyguard.
- On pairs connect all wires in parallel to master except Green.
- Green stall wire must connect to both master and slave.
LCN
2500 / 9300 Series
Notes
Use LCN Retro Harness:
Part Number: 761469
Wire the same as Doromatic Astroswing installations.
Motion Access
Condor 506
Uses J-9 terminal connections for all functions.
Quad Systems
ES-500
Uses CN2 and CN6 connections for activation, safety, power, and motor monitoring.
Stanley
Tandem L-Shape Control
Notes
- On six-pin Molex connector:
- Mat Safety input aligns with Yellow and Orange wires.
- Stall Safety input is adjacent.
- Select Timer Logic mode.
MP (HDLE) Control
Notes
- Magicswing: Black motor wire is positive.
- MagicForce:
- RH Operator: Black positive.
- LH Operator: White positive.
- Set Stanley S-2 switches 1 and 3 OFF.
521 Control
Option 1 – Motor Monitoring
Observe motor polarity requirements.
Option 2 – Data Monitoring
Install:
- 300Ω
- 5 Watt resistor
between TB1 Pin 1 and Pin 8.
Set Safety Logic to Sensor.
Tormax
TDA
Notes
For simultaneous pairs or double egress applications, contact OPTEX for additional wiring instructions.
iMotion 1301
Connections shown apply to single-door installations.
For simultaneous pairs or double egress applications, contact OPTEX.
TTX2 Smart Drive
Wiring
Function | Connection |
Stall | Pins 14 & 15 |
Activate | Pins 4 & 5 |
Safety | Pins 18 & 19 |
Motor (-) | Pin 11 |
Motor (+) | Pin 12 |
Power | Pin 20 |
Power | Pin 17 |
Programming
On TTX:
- Solid 2 → Flashing 2
- Solid 4 → Flashing 2
On 905 Controller:
- DIP 1 = Up
- DIP 2 = Up
- DIP 4 = Down
Pairs may require DPDT relays to isolate activation and safety inputs.